1) Model Name : REF.SM.01
	2) Meter Defination : 1 Phase , 2 Wires , 4 Tariffs , Demantmetered , Outdoor , Prepayment Meter
	3) Accuracy Class : Mode B ( Class 1 )
	4) Referance Voltage : 230/400V ( Compitable 240 / 400V )
	5) Wide InputVoltage: 120V(Minimum) – 300V(Maksimum) ( Phase To Notr )
	6) Frequency : 50Hz
	7) Take Off Current : 20mA ( 5A / 200 in standart )
	8) Minimum Current : 250mA
	9) Referance Current : 5A
	10) Maksimum Current : 100A
	11) IP Class : IP54
	12) Protection Class : 2
	13) Humidity Rate : %95
	14) Operating Temp. : -40 , +80 °C
	15) Mechanical Env. : M1 ( According to 2004 / 22 / EC directive )
	16) Elektromagnetic : E2 (According to 2004 / 22 / EC directive )
	17) Voltage Circuit : < 1W (Should be < 2W in standart)
	18) Current Circuit : < 0.2W (Should be < 1W in standart)
	19) Total Power : < 1.2W (Total power consumption per phase)
	20) ESD : 8KV with contacts , 15KV by air
	21) Impulse Voltage : 12kV
	22) Meter Constant : 1000imp/kWh
	23) LCD : 6 + 3
	24) Comm. Rate : 300 – 9600 ( IEC 62056-21 Mode C )
	25) Interface1 : Optical Port ( 300 – 9600 ) ( IEC 62056-21 Mode C )(Indepandent)
	26) Interface2 : Rs485 Port ( 300 – 9600 ) ( IEC 62056-21 Mode C )( Indepandent)
	27) Generator Tariffi : Generator tariff detection with generator auxiliary contact input
	28) Sys. Battary Life : 10Year
	29) Shutoff Structure : Internal Latch Relay
	30) Security Logs : Up Cover , Terminal Cover ext.
	31) Data Logs : 1 Year
	32) Related Standarts : EN 62056-11 , EN 62053-21
	33) Related Docs : MID compatibility
	34) Regulations : Compatible with Tedaş requirement
	35) Technology : Contactless communication is provided through the Mifare / RFID technology
	36) RFField Detection: Automatic or push button activation ( Optional )
	37) Alarm Circuit : Cancelable acoustic alarm circuit
	38) Contour back-up : Available (Optional)
	39) Compatibility : Since it is possible to write to the desired sectors, more than one application can be run at the same time with the same card.
	40) Credit : Cutting the counter at the desired time periods with the possibility of credit is provided.
	41) Easy to use : Easy installation and easy to use feature by means of an Accounting Program. (Optional)